Fundamentals of dust explosion protection

Fundamental principles:
The manufacturer of operating devices for areas rendered potentially explosive through dust must indicate the maximum surface temperature of all devices that dust can penetrate (usually expressed in °C - indication of the temperature class should be avoided here). This temperature is part of the dust Ex-designation.


    Designation examples:
    II 2 D T90 °C IP64, II 2 D Ex td A21 T90 °C IP64
    (If the ignition protection type is based on the housing, the housing protection
    rating should also be stated as an IP Code). or II 2 D Ex iaD 21 T96 °C

(This device has already been approved according to the new IEC de-jure standard "Intrinsic Dust Safety - iaD". This de-jure standard specifies that the designation also contains the corresponding zone - in this case 21)

Dust explosion protection - temperature:

Combustion and explosion parameters for dusts depend on the their condition. Parameters that affect combustion and explosion behaviour include particle size, particle shape, water content, purity and where applicable the content of the flammable solvents.
The particle size distribution and the mean value (value for average particle size) should also be known.

In accordance with 1999/92/EG Directive (ATEX 137, replacing: ATEX 118a),the system operator /employer is obliged to make a hazard assessment and must therefore be aware of the minimum glow temperature of the dust.

There are simple calculations to determine the two "temperatures" and they are carried out thus:
    a) Limit temperature 1 = 2/3 of minimum ignition temperature
    b) Limit temperature 2 = minimum ignition temperature* minus 75 °K

These two limit temperatures must now be examined to confirm which guarantees the greater safety.

    Example 1:
    Minimum ignition temperature = +330 °C,
    minimum glow temperature = +300 °C:
    a) Limit temperature 1     =     2/3    x   +330 °C     =     +220 °C
    b) Limit temperature 2     =     +300 °C   - 75 °K      =     +225 °C
    Greater safety: Limit temperature (1) = +220 °C
    Here a device with a max. surface temperature in the event of failure <= +220 °C
    must be used. As stated, the device designation includes a corresponding value.

    Example 2:
    Minimum ignition temperature = +186 °C,
    minimum glow temperature = +180 °C:
    a) Limit temperature 1     =     2/3    x   +186 °C     =     +124 °C
    b) Limit temperature 2     =     +180 °C   - 75 °K      =     +105 °C
    Greater safety: Limit temperature (2) = +105 °C
    Here a device with a max. surface temperature in the event of failure <= +105 °C
    must be used.

*The value for the glow temperature applies with a dust layer thickness of 5mm. The temperature safety distance must be increased for larger layer thicknesses.

Exhibitions 2010


22nd - 24th March
cippe 2010
Beijing, China


12th - 14th April
STM-9
Jubail, Saudi Arabia


19th - 23rd April
Interkama
Hanover, Germany


7th - 12th June
Interschutz
Leipzig, Germany


9th June
MSR Rheinland
Leverkusen, Germany


15th September
MSR Südwest
Frankenthal, Germany


16th September
M+R Brussels
Brussel, Belgium


12th - 14th October
Maintain
Munich, Germany


3rd November
MSR Rhein-Ruhr
Duisburg, Germany


23rd - 25th November
PMRExpo 2010
Cologne, Germany

Catalog

Please find all information to our products in our current catalogue.

Order now!

ATEX - be informed!

Do you know about intrinsical safety, ATEX and its directives?

get some information here...